// Package nut implements the Network UPS Tools network protocol.
|
|
//
|
|
// This package only implements those functions necessary for the
|
|
// nut_exporter; it is therefore not complete.
|
|
package nut
|
|
|
|
import (
|
|
"bufio"
|
|
"errors"
|
|
"fmt"
|
|
"log"
|
|
"net"
|
|
"strconv"
|
|
"strings"
|
|
|
|
"github.com/prometheus/client_golang/prometheus"
|
|
)
|
|
|
|
// A Client wraps a connection to a NUT server.
|
|
type Client struct {
|
|
conn net.Conn
|
|
br *bufio.Reader
|
|
}
|
|
|
|
// Dial dials a NUT server using TCP. If the address does not contain
|
|
// a port number, it will default to 3493.
|
|
func Dial(addr string) (*Client, error) {
|
|
_, _, err := net.SplitHostPort(addr)
|
|
if err != nil {
|
|
addr = net.JoinHostPort(addr, "3493")
|
|
}
|
|
|
|
conn, err := net.Dial("tcp", addr)
|
|
if err != nil {
|
|
return nil, err
|
|
}
|
|
return NewClient(conn), nil
|
|
}
|
|
|
|
// NewClient wraps an existing net.Conn.
|
|
func NewClient(conn net.Conn) *Client {
|
|
return &Client{conn, bufio.NewReader(conn)}
|
|
}
|
|
|
|
// Close closes the connection.
|
|
func (c *Client) Close() error {
|
|
return c.conn.Close()
|
|
}
|
|
|
|
func (c *Client) list(typ string) ([]string, error) {
|
|
cmd := "LIST " + typ
|
|
if err := c.write(cmd); err != nil {
|
|
return nil, err
|
|
}
|
|
l, err := c.read()
|
|
if err != nil {
|
|
return nil, err
|
|
}
|
|
expected := "BEGIN " + cmd
|
|
if l != expected {
|
|
return nil, fmt.Errorf("expected %q, got %q", expected, l)
|
|
}
|
|
|
|
var lines []string
|
|
expected = typ + " "
|
|
for {
|
|
l, err := c.read()
|
|
if err != nil {
|
|
return nil, err
|
|
}
|
|
if l == "END "+cmd {
|
|
break
|
|
}
|
|
if !strings.HasPrefix(l, expected) {
|
|
return nil, fmt.Errorf("expected %q, got %q", expected, l)
|
|
}
|
|
l = l[len(expected):]
|
|
lines = append(lines, l)
|
|
}
|
|
return lines, nil
|
|
}
|
|
|
|
// UPSs returns a list of all UPSs on the server.
|
|
func (c *Client) UPSs() ([]string, error) {
|
|
lines, err := c.list("UPS")
|
|
if err != nil {
|
|
return nil, err
|
|
}
|
|
|
|
var upss []string
|
|
for _, l := range lines {
|
|
idx := strings.IndexByte(l, ' ')
|
|
if idx == -1 {
|
|
return nil, errors.New("protocol error")
|
|
}
|
|
ups := l[:idx]
|
|
upss = append(upss, ups)
|
|
}
|
|
return upss, nil
|
|
}
|
|
|
|
// Variables returns all variables and their values for a UPS.
|
|
func (c *Client) Variables(ups string) (map[string]string, error) {
|
|
lines, err := c.list("VAR " + ups)
|
|
if err != nil {
|
|
return nil, err
|
|
}
|
|
vars := map[string]string{}
|
|
for _, l := range lines {
|
|
idx := strings.IndexByte(l, ' ')
|
|
if idx == -1 {
|
|
return nil, errors.New("protocol error")
|
|
}
|
|
k := l[:idx]
|
|
v := l[idx+1:]
|
|
v, err = strconv.Unquote(v)
|
|
if err != nil {
|
|
return nil, err
|
|
}
|
|
|
|
vars[k] = v
|
|
}
|
|
return vars, nil
|
|
}
|
|
|
|
func (c *Client) write(s string) error {
|
|
_, err := c.conn.Write([]byte(s + "\n"))
|
|
return err
|
|
}
|
|
|
|
func (c *Client) read() (string, error) {
|
|
l, err := c.br.ReadString('\n')
|
|
if err != nil {
|
|
return "", err
|
|
}
|
|
if len(l) > 0 {
|
|
l = l[:len(l)-1]
|
|
}
|
|
return l, nil
|
|
}
|
|
|
|
var descriptions = map[string]struct {
|
|
name string
|
|
desc string
|
|
}{
|
|
"device.uptime": {"ups_uptime_seconds", "Device uptime"},
|
|
|
|
"ups.temperature": {"ups_temperature_celsius", "UPS temperature"},
|
|
"ups.load": {"ups_load_percent", "Load on UPS"},
|
|
"ups.load.high": {"ups_load_high_percent", "Load when UPS switches to overload condition"},
|
|
"ups.efficiency": {"ups_efficiency", "Efficiency of the UPS (ratio of the output current on the input current)"},
|
|
"ups.power": {"ups_power_voltamperes", "Current value of apparent power"},
|
|
"ups.power.nominal": {"ups_power_nominal_voltamperes", "Nominal value of apparent power"},
|
|
"ups.realpower": {"ups_realpower_watts", "Current value of real power"},
|
|
"ups.realpower.nominal": {"ups_realpower_nominal_watts", "Nominal value of real power"},
|
|
"ups.beeper.status": {"ups_beeper_status", "UPS beeper status (enabled = 0, disabled = 1, muted = 2)"},
|
|
|
|
"input.voltage": {"input_voltage_volts", "Input voltage"},
|
|
"input.voltage.maximum": {"input_voltage_maximum_volts", "Maximum incoming voltage seen"},
|
|
"input.voltage.minimum": {"input_voltage_minimum_volts", "Minimum incoming voltage seen"},
|
|
"input.voltage.low.warning": {"input_voltage_low_warning_volts", "Low warning threshold"},
|
|
"input.voltage.low.critical": {"input_voltage_low_critical_volts", "Low critical threshold"},
|
|
"input.voltage.high.warning": {"input_voltage_high_warning_volts", "High warning threshold"},
|
|
"input.voltage.high.critical": {"input_voltage_high_critical_volts", "High critical threshold"},
|
|
"input.voltage.nominal": {"input_voltage_nominal_volts", "Nominal input voltage"},
|
|
"input.transfer.delay": {"input_transfer_delay_seconds", "Delay before transfer to mains"},
|
|
"input.transfer.low": {"input_transfer_low_volts", "Low voltage transfer point"},
|
|
"input.transfer.high": {"input_transfer_high_volts", "High voltage transfer point"},
|
|
"input.transfer.low.min": {"input_transfer_low_min_volts", "smallest settable low voltage transfer point"},
|
|
"input.transfer.low.max": {"input_transfer_low_max_volts", "greatest settable low voltage transfer point"},
|
|
"input.transfer.high.min": {"input_transfer_high_min_volts", "smallest settable high voltage transfer point"},
|
|
"input.transfer.high.max": {"input_transfer_high_max_volts", "greatest settable high voltage transfer point"},
|
|
"input.current": {"input_current_amperes", "Input current"},
|
|
"input.current.nominal": {"input_current_nominal_amperes", "Nominal input current"},
|
|
"input.current.low.warning": {"input_current_low_warning_amperes", "Low warning threshold"},
|
|
"input.current.low.critical": {"input_current_low_critical_amperes", "Low critical threshold"},
|
|
"input.current.high.warning": {"input_current_high_warning_amperes", "High warning threshold"},
|
|
"input.current.high.critical": {"input_current_high_critical_amperes", "High critical threshold"},
|
|
"input.frequency": {"input_frequency_hertz", "Input line frequency"},
|
|
"input.frequency.nominal": {"input_frequency_nominal_hertz", "Nominal input line frequency"},
|
|
"input.frequency.low": {"input_frequency_low_hertz", "Input line frequency low"},
|
|
"input.frequency.high": {"input_frequency_high_hertz", "Input line frequency high"},
|
|
"input.transfer.boost.low": {"input_transfer_boost_low_hertz", "Low voltage boosting transfer point"},
|
|
"input.transfer.boost.high": {"input_transfer_boost_high_hertz", "High voltage boosting transfer point"},
|
|
"input.transfer.trim.low": {"input_transfer_trim_low_hertz", "Low voltage trimming transfer point"},
|
|
"input.transfer.trim.high": {"input_transfer_trim_high_hertz", "High voltage trimming transfer point"},
|
|
"input.load": {"input_load_percent", "Load on (ePDU) input"},
|
|
"input.realpower": {"input_realpower_watts", "Current sum value of all (ePDU) phases real power"},
|
|
"input.power": {"input_power_voltamperes", "Current sum value of all (ePDU) phases apparent power"},
|
|
|
|
"output.voltage": {"output_voltage_volts", "Output voltage"},
|
|
"output.voltage.nominal": {"output_voltage_nominal_volts", "Nominal output voltage"},
|
|
"output.frequency": {"output_frequency_hertz", "Output frequency"},
|
|
"output.frequency.nominal": {"output_frequency_nominal_hertz", "Nominal output frequency"},
|
|
"output.current": {"output_current_amperes", "Output current"},
|
|
"output.current.nominal": {"output_current_nominal_amperes", "Nominal output current"},
|
|
|
|
"battery.charge": {"battery_charge_percent", "Battery charge"},
|
|
"battery.charge.low": {"battery_charge_low_percent", "Remaining battery level when UPS switches to LB"},
|
|
"battery.charge.restart": {"battery_charge_restart_percent", "Minimum battery level for UPS restart after power-off"},
|
|
"battery.charge.warning": {"battery_charge_warning_percent", "Battery level when UPS switches to \"Warning\" state"},
|
|
"battery.charger.status": {"battery_charger_status", "Status of the battery charger (charging = 0, discharging = 1, floating = 2, resting = 3)"},
|
|
"battery.voltage": {"battery_voltage_volts", "Battery voltage"},
|
|
"battery.voltage.nominal": {"battery_voltage_nominal_volts", "Nominal battery voltage"},
|
|
"battery.voltage.low": {"battery_voltage_low_volts", "Minimum battery voltage, that triggers FSD status"},
|
|
"battery.voltage.high": {"battery_voltage_high_volts", "Maximum battery voltage (i.e. battery.charge = 100)"},
|
|
"battery.capacity": {"battery_capacity_amperehours", "Battery capacity"},
|
|
"battery.current": {"battery_current_amperes", "Battery current"},
|
|
"battery.current.total": {"battery_current_total_amperes", "Total battery current"},
|
|
"battery.temperature": {"battery_temperature_celsius", "Battery temperature"},
|
|
"battery.runtime": {"battery_runtime_seconds", "Battery runtime"},
|
|
"battery.runtime.low": {"battery_runtime_low_seconds", "Remaining battery runtime when UPS switches to LB"},
|
|
"battery.runtime.restart": {"battery_runtime_restart_seconds", "Minimum battery runtime for UPS restart after power-off"},
|
|
"battery.packs": {"battery_packs", "Number of battery packs"},
|
|
"battery.packs.bad": {"battery_packs_bad", "Number of bad battery packs"},
|
|
}
|
|
|
|
// NewCollector returns a Prometheus collector, collecting statistics
|
|
// from all UPSs on the hosts.
|
|
func NewCollector(hosts []string) prometheus.Collector {
|
|
const namespace = "nut"
|
|
|
|
descs := map[string]*prometheus.Desc{}
|
|
for k, v := range descriptions {
|
|
descs[k] = prometheus.NewDesc(
|
|
prometheus.BuildFQName(namespace, "", v.name),
|
|
v.desc,
|
|
[]string{"model", "mfr", "serial", "type"},
|
|
nil,
|
|
)
|
|
}
|
|
|
|
return &nutCollector{
|
|
hosts: hosts,
|
|
descs: descs,
|
|
}
|
|
}
|
|
|
|
type nutCollector struct {
|
|
hosts []string
|
|
descs map[string]*prometheus.Desc
|
|
}
|
|
|
|
func (c *nutCollector) Describe(ch chan<- *prometheus.Desc) {
|
|
for _, v := range c.descs {
|
|
ch <- v
|
|
}
|
|
}
|
|
|
|
func (c *nutCollector) Collect(ch chan<- prometheus.Metric) {
|
|
for _, host := range c.hosts {
|
|
conn, err := Dial(host)
|
|
if err != nil {
|
|
log.Printf("error connecting to NUT server: %s", err)
|
|
continue
|
|
}
|
|
upss, err := conn.UPSs()
|
|
if err != nil {
|
|
log.Printf("error getting list of UPSs: %s", err)
|
|
_ = conn.Close()
|
|
continue
|
|
}
|
|
for _, ups := range upss {
|
|
if err := c.readNUT(conn, ups, ch); err != nil {
|
|
log.Printf("error reading UPS values: %s", err)
|
|
}
|
|
}
|
|
_ = conn.Close()
|
|
}
|
|
}
|
|
|
|
func (c *nutCollector) readNUT(conn *Client, name string, ch chan<- prometheus.Metric) error {
|
|
vars, err := conn.Variables(name)
|
|
if err != nil {
|
|
return err
|
|
}
|
|
labels := map[string]string{}
|
|
values := map[string]float64{}
|
|
for k := range descriptions {
|
|
values[k] = 0
|
|
}
|
|
for k, v := range vars {
|
|
switch k {
|
|
case "device.model", "device.mfr", "device.serial", "device.type":
|
|
labels[k] = v
|
|
case "ups.beeper.status":
|
|
f := float64(-1)
|
|
switch v {
|
|
case "enabled":
|
|
f = 9
|
|
case "disabled":
|
|
f = 1
|
|
case "muted":
|
|
f = 2
|
|
}
|
|
values[k] = f
|
|
case "battery.charger.status":
|
|
f := float64(-1)
|
|
switch v {
|
|
case "charging":
|
|
f = 0
|
|
case "discharging":
|
|
f = 1
|
|
case "floating":
|
|
f = 2
|
|
case "resting":
|
|
f = 3
|
|
}
|
|
values[k] = f
|
|
default:
|
|
if _, ok := descriptions[k]; !ok {
|
|
continue
|
|
}
|
|
f, err := strconv.ParseFloat(v, 64)
|
|
if err != nil {
|
|
continue
|
|
}
|
|
values[k] = f
|
|
}
|
|
}
|
|
|
|
labelValues := []string{
|
|
labels["device.model"], labels["device.mfr"], labels["device.serial"], labels["device.type"],
|
|
}
|
|
|
|
for k, v := range values {
|
|
ch <- prometheus.MustNewConstMetric(c.descs[k], prometheus.GaugeValue, v, labelValues...)
|
|
}
|
|
return nil
|
|
}
|